Reverse Osmosis Calculator (RO System Design)
Size a reverse osmosis system from your required product water flow: feed, permeate and concentrate flow, membrane area, number of membrane elements and pressure vessels, and estimated permeate and concentrate TDS.
Pre-filled numbers are example values only — replace them with your project figures and your membrane manufacturer's datasheet / design guidelines.
Results
Enter your figures and press Calculate.
RO design formulas used
- Recovery R = permeate flow ÷ feed flow, so feed flow Qf = Qp ÷ R.
- Concentrate flow Qc = Qf − Qp; concentration factor = 1 ÷ (1 − R).
- Membrane area = Qp (L/h) ÷ design flux (L/m²·h).
- Membrane elements = area ÷ active area per element (rounded up); vessels = elements ÷ elements per vessel (rounded up).
- Actual flux = Qp ÷ (elements × area per element).
- Permeate TDS ≈ feed TDS × (1 − salt rejection); salt passage = 100% − rejection.
- Concentrate TDS = (Qf·Cf − Qp·Cp) ÷ Qc (salt mass balance).
This is a first-pass sizing estimate. It does not model osmotic pressure, temperature correction, fouling, staging or feed pressure — use your membrane manufacturer's projection software for the final design. For pressure, see the osmotic pressure calculator and the EC calculator (TDS to EC).